J1000 INVERTER 2.2kW/1.5kW, CIMR-JC4A0005BAA

Call for Price

Use code: “YaskawaFree” at checkout for free delivery when you buy a J1000 or V1000 series inverter

SKU: CIMR JC4A0005BAA Category: Tags: , , , , ,

Description

The J1000 series is in the process of being discontinued. We advise customers to upgrade to the GA500 series equivalent. Please contact our sales team for more information on transitioning from the J1000 to GA500.

 

The Yaskawa J1000 Inverter is a compact variable speed inverter drive providing efficient, high performance features in a compact package. All of Yaskawa’s J1000 range of inverters are designed with simple “plug and play” installation in mind, offering user friendly parameter programming while still being highly adaptable for a variety of applications. The JC4A line is designed to run on a 380 to 480 V, three phase (3ph) line. 

More information about Yaskawa J1000 Inverters can be found here: J1000 Brochure

Goodwin Electronics also offers installation and panel design options for J1000 inverters, for more information on this service please feel free to contact us here: Contact Us

Model NumberCIMR-JC4A0005BAA
Voltage Class400 V
OutputMotor Output (kW) Normal Duty2.2
Motor Output (kW) Heavy Duty1.5
Rated Output (A) Normal Duty5.4
Rated Output (A) Heavy Duty4.8
Rated Output Power (kVA) Normal Duty4.1
Rated Output Power (kVA) Heavy Duty3.7
Max. Output VoltageThree-phase 380 to 480 V (relative to input voltage)
Max. Output Frequency400 Hz
InputRated Input VoltageThree Phase 380 to 480 V +10% / -15%
Rated Input Frequency50 / 60 Hz, ±5%
Control MethodsV/F Control
Frequency Control Range0.01 to 400 Hz
Frequency AccuracyDigital Input: ±0.01% of the Max. Output Freq. (-10°c to +50°c)
Analog Input: ±0.05% of the Max. Output Freq. (25°c ±10°c)
Frequency Setting ResolutionDigital Input: 0.01 Hz
Analog Input: 1/1000 of Max. Freq.
Starting Torque150% / 3 Hz
Speed Control Range1:20

 

Motor ProtectionMotor overheat protection based on output current
Momentary Overcurrent ProtectionDrive stops when output current exceeds 200% of Heavy Duty Rating
Overload Protection120% for 60 sec. at normal duty, 150% for 60 sec. at heavy duty
Overvoltage ProtectionStops when DC bus exceeds approx. 410 V
Undervoltage ProtectionStops when DC bus Voltage falls below approx. 160 V
Drive Overheat ProtectionProtected by thermistor

 

Areas of UseIndoors
Ambient Temperature-10 to +50°C (IP20 open chassis)
Humidity95 RH% or less (no condensation)
Storage Temperature-20 to +60°C (short term temperature during transportation
AltitudeMax. 1000m (output derating of 1% per 100m above 1000m, max. 3000m)
Shock10 to 20 Hz (9.8 m/s²) max., 20 to 55 Hz (5.9m/s²) max.

Additional information

Weight 1.9 kg
Dimensions 154 × 108 × 128 mm